Case study A for offices to show where automatic sprinklers have the greatest impact
This article was originally published as part of The impact of automatic sprinklers on building design, an independent report produced by WSP, sponsored by the Business Sprinkler Alliance (BSA), published in September 2017.
See also: Case study B for offices to show where automatic sprinklers have the greatest impact.
This case study illustrates the details contained herein for offices to show where automatic sprinklers are likely to have the greatest impact.
The example features a six-storey office building located in central London with 15,000m2 GIA and fully-glazed façades. The design guidance used is BS 9999 (no fire engineering) and the designs with and without automatic sprinklers are compared in terms of capital cost.
- Offices 50x50 m2 .
- 6 storeys – c. 24m.
- Separation distances are; Northern side 20m, Eastern side 10m, Southern side 10m, Western side 5m.
- Glazed façade.
- 4 staircases.
![]() |
![]() |
![]() |
Firstly, the design impacts of incorporating an automatic sprinkler system on the fire protection measures are demonstrated in Table 6-2. Secondly, cost analysis of the impact is shown in Table 6-3.
[Table 6-2 Impact of sprinklers on the required fire protection measures for Building A]
BUILDING A | Without Sprinklers | With Sprinklers |
Fire-rated façade area required |
Northern side (17%) = 204 m2 Southern side (67%) = 804 m2 Eastern side (67%) = 804 m2 Western side (80%) = 960 m2 |
Northern side (0%) = 0 m2 Southern side (34%) = 408 m2 Eastern side (34%) = 408 m2 Western side (60%) = 720 m2 |
Stairs minimum width | 1276 mm Stairs area 61.25m2 per floor | 1120 mm Stairs area 53.75m2 per floor |
Structural fire protection rating | 90 minutes | 60 minutes |
Dry risers | 3 | 2 |
[Table 6-3 Cost analysis of incorporating sprinklers in Building A]
BUILDING A | Without Sprinklers | With Sprinklers |
Sprinklers installation cost | – | £328,750 |
Façade cost13 |
Non FR façade= 2,028m2 x £600/m2 = £1,216,800 90min-FR façade= 2,772m2 x £2,200/m2 = £6,098,400 Total = £7,315,200 |
Non FR façade= 3,264m2 x £600/m2 = £1,958,400 60min-FR façade = 1,536m2 x £1,700/m2 = £2,611,200 Total = £4,569,600 |
Structural fire protection cost |
90min-FR = 15,000m2 x £44.38/m2 = £665,700 |
60min-FR = 15,000m2 x £21.57/m2 = £323,550 |
Rental yields derived from changes to net internal area | – |
45m2 x £650/m2/yr = £29,250/yr |
Dry risers costs |
3 x £1,500/landing x 6 floors = £27,000 |
2 x £1,500/landing x 6 floors = £18,000 |
Total costs | £8,007,900 | £5,239,900 - £29,250/yr |
Total cost impact of sprinklers
Capital cost impact = £2,768,000 saved by including sprinklers
Rental yield = £29,250/yr greater income by including sprinklers
Verdict: Installing automatic sprinklers in Building A can accumulate initial capital cost savings of c. £2.8M with an additional rentable area that can generate about £30k/yr. The additional rental income alone would pay for the automatic sprinkler system in 11 years. These values need to be used carefully however since there may be alternative measures that could be considered to reduce the cost of the façade such as an increase in compartmentation. This is particularly relevant here where the façade cost is high due to the need for fire-rated glazing. However, in this example automatic sprinklers have been shown that they can have a positive financial impact on a project.
Reference [13] Glazed fire-rated façade assumed required for aesthetic reasons by the client.
--Business Sprinkler Alliance.
[edit] Related articles on Designing Buildings
- Automatic fire sprinkler.
- Automatic fire sprinkler systems: A good practice guide.
- Automatic sprinkler system design and operation.
- Business Sprinkler Alliance.
- Case study B for offices to show where automatic sprinklers have the greatest impact.
- Costs of water automatic sprinkler systems.
- Design benefits of automatic sprinkler systems granted under approved document B
- Drenchers.
- Fire.
- Making the case for sprinklers and dispelling myths.
- Overview of automatic sprinkler system design and operation
- Sprinkler systems explained: A guide to sprinkler installation standards and rules.
- Sprinklers.
- The cost efficiency of different combinations of fire protection measures.
- The impact of automatic sprinklers on building design.
Featured articles and news
Focussing on the practical implementation of electrification.
Sustainable Urban Drainage and Biodiversity
Awards for champions of these interconnected fields now open.
Microcosm of biodiversity in balconies and containers
Minor design adaptations for considerable biodiversity benefit.
CIOB student competitive construction challenge Ireland
Inspiring a new wave of Irish construction professionals.
Challenges of the net zero transition in Scotland
Skills shortage and ageing workforce hampering Scottish transition to net zero.
Private rental sector, living standards and fuel poverty
Report from the NRH in partnership with Impact on Urban Health.
.Cold chain condensing units market update
Tracking the evolution of commercial refrigeration unit markets.
Attending a conservation training course, personal account
The benefits of further learning for professsionals.
Restoring Alexander Pope's grotto
The only surviving part of his villa in Twickenham.
International Women's Day 8 March, 2025
Accelerating Action for For ALL Women and Girls: Rights. Equality. Empowerment.
Lack of construction careers advice threatens housing targets
CIOB warning on Government plans to accelerate housebuilding and development.
Shelter from the storm in Ukraine
Ukraine’s architects paving the path to recovery.
BSRIA market intelligence division key appointment
Lisa Wiltshire to lead rapidly growing Market Intelligence division.
A blueprint for construction’s sustainability efforts
Practical steps to achieve the United Nations Sustainable Development Goals.
Timber in Construction Roadmap
Ambitious plans from the Government to increase the use of timber in construction.
ECA digital series unveils road to net-zero.
Retrofit and Decarbonisation framework N9 launched
Aligned with LHCPG social value strategy and the Gold Standard.